The clean laboratory is mainly through that means, to achieve control of indoor air dust, humidity and pressure, temperature and concentration of bacteria and application of clean technology and environmental parameters to achieve the required cleanliness, temperature and humidity and airflow velocity.
Basic requirements of clean laboratory design:
1. The layout is compact, is reasonable, meet the requirement of laboratory operations and air cleanliness level, makes every effort to the principles of scientific nature and economy at the same time, considering the laboratory requirement and the development and optimal operating cost.
2. Set the air shower, clean room entrance is in, can effectively remove the body with dust, decrease the dust in the clean room, air shower at the same time also have the effect of the damper, preventing the unclean air by the door into the clean area.
3. The clean room shall supply a certain proportion of fresh air to the room, and then enter the laboratories to compensate the exhaust air to ensure the positive pressure and staff needs.
4.Airflow with air volume control valve type number to control different requirements of clean level area, as well as the adjustment of the pressure gradient, guarantees the air with the "clean" to "pollution" area, clean room pressure differential between different levels of 5 or more pa, clean room and outside differential pressure for 10 or more pa.
5. Install purple lamp sterilization device in clean room.
6. The transmission window is made of all-stainless steel, mechanical interlocking control, and internal sterilization device.
7. Observe the window as a closed and clean window, and the door is air-tight and clean.
8. Power supply: AC220V/ 380v-50hz.
9. Indoor noise is not equal to 60db (A).
10.The exhaust vents are equipped with high efficiency strainers. The air outlet is equipped with high efficiency filtration static pressure box to achieve air intake and clean, and it is convenient to replace the high efficiency filter.
11.The indoor air outlet should be located in the area with the highest risk of pollution. The indoor air outlet should be located in the area with the highest risk of pollution.
12.The return air port automatically adjusts the indoor pressure with the residual pressure valve to keep the positive pressure clean